Part Number Hot Search : 
C40H0 2SPBF LE45CZ LND3843B UPA1764 IRFR024N ABE0102 FDC634P
Product Description
Full Text Search
 

To Download AS168X-CB1DH500N Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Product description
The AS168X is a thermal magnetic high performance CBE to IEC 934 and a supplementary protector to UL 1077. It is capable of drastically limiting the let-through energy in case of short circuit interruptions. The series is available in units from one to four poles for use in AC and DC circuits. Multipole devices are connected internally and at the handle for simultaneous operation. This applies also to combinations with the switched neutral pole. Well designed screw type terminals at line and load side are provided for safe and easy connection to line and load. They accept #16 to 4 AWG / 1,5 to 25 mm2. The AS168X is suitable as supplementary protector under UL 1077 / EN 60934 or as Manual Motor Controller according UL 508 / CSA 22.2 14. Thus the Breaker has a high versatility and is suitable for many functions: * Motor overload protection (thermal and magnetic) * Motor starting across-the-line (direct-on-line) * Motor starting with motor disconnect (cos phi 0,4 - 0,5) * Motor group installation (short capacity 5 kA) * Control circuits
AS168X
Produktebeschreibung
Der AS168X ist ein thermisch magnetischer Hochleistungs CBE, der in der Lage ist, bei Kurzschluss-Abschaltungen den Durchlass-Strom drastisch zu reduzieren. Die Serie ist erhaltlich in Ausfuhrungen mit einem bis vier geschutzten Polen, die in Wechselstrom- oder Gleichstromnetzen eingesetzt werden konnen. Mehrpolige CBE sind intern und beim Kipphebel mechanisch verbunden, um gleichzeitiges Schalten zu gewahrleisten. Dies gilt auch fur eine Kombination mit dem schaltbaren Null-Leiter Pol. Raffiniert konstruierte Liftklemmen auf der Eingangs- und Abgangsseite ermoglichen einen bequemen Netz- und Lastanschluss. Die Klemmen sind zum Anschluss von Leitern mit 1,5 bis 25 mm2 Querschnitt geeignet, (AWG #16...4). Der AS168X ist einsetzbar als Gerateschutzschalter nach UL 1077 / EN 60934 oder als Motorschutzschalter nach UL 508 bzw. CSA 22.2 14. Der Schalter ist somit vielseitig einsetzbar und eignet sich fur folgende Funktionen: * Motor overload protection (thermisch und magnetisch) * Motor starting across-the-line (direct-on-line) * Motor starting with motor disconnect (cos phi 0,4 - 0,5) * Motor group installation (short capacity 5 kA) * Control circuits
Accessories * Auxiliary contact module Each auxiliary contact module contains one contact, either normally open or normally closed. * Signal contact module Signal contact modules are linked internally with the protected poles but not linked at the handles. Contacts are actuated by a fault condition at the protected poles, not by the manual operation of the CBE. * Relay trip module The relay trip module can be used for remote tripping of the adjacent poles by applying a voltage to the module's terminal. * Switched neutral pole (factory assembled) This module allows to automatically open the neutral line when the protected poles have been tripped. Zubehor * Hilfskontakte Jedes Modul ist mit einem Offnungs- oder Schliesskontakt ausgerustet. * Signalkontakt-Modul Signalkontakt Module sind intern mit dem benachbarten Pol verbunden, weisen aber keine Verbindung der Kipphebel auf. Daher schaltet dieses Modul nur beim automatischen Auslosen der benachbarten Pole, aber nicht bei manueller Betatigung. * Fremdauslosung Dieses Modul kann fur die Fernauslosung der benachbarten Pole mittels eines Spannungspulses verwendet werden. * Schaltbarer Neutralleiter Pol Dieses Modul erlaubt ein automatisches Offnen des Neutralleiters wenn die geschutzten Pole auslosen.
Features * * * * * * Excellent short circuit performance (up to 10 kA) High limits of discrimination (due to energy limitation) Wide choice of characteristics (Adaptability) Availability of AC and DC in the same frame size Compact, finger safe design Ease installation (on DIN rail) Besondere Merkmale * Exzellentes Abschaltvermogen (bis zu 10 kA) * Ermoglicht hohe Selektivitatsgrenzen durch energiebegrenzendes Schalten * Grosse Auswahl von Auslosekennlinien Anpassungsfahigkeit an die Applikations-Bedingungen * Ausfuhrungen fur Wechsel- und Gleichstrom in gleicher Gehausegrosse * Kompakte fingersichere Bauweise * Einfache Montage (DIN-Schiene)
Applications * Industrial machines * Automation * Aircondition, ventilation * Transformers * Power supplies * Telecom systems * Computer systems * Test systems * Medical equipments
Anwendungen * Industrieller Maschinenbau * Automation * Klima- und Ventilationsanlagen * Transformatoren * Stromversorgungen *Telekommunikationsanlagen * Computersysteme * Testsysteme * Medizinalgerate
www.schurter.com
123
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Effect of ambient temperature
AC-breakers are calibrated for an ambient temperature of +40C, DC-breakers for +23C. To determine the rated current for a lower or higher ambient temperature, use a correction factor from the table below:
AS168X
Einfluss der Umgebungstemperatur
AC-Schalter sind fur eine Umgebungstemperatur von +40C geeicht, DC-Schalter fur +23C. Zur Bestimmung des Nennstromes fur eine tiefere oder hohere Umgebungstemperatur ist ein Korrekturfaktor gemass untenstehender Tabelle zu verwenden: Umgebungstemperatur [C] -20 -5 0 +10 +23 +30 +40 +50 +60 Korrekturfaktor AC-Version DC-Version 0,78 0,82 0,83 0,87 0,91 0,95 1,00 1,05 1,11 0,80 0,87 0,90 0,95 1,00 1,05 1,10 1,20 1,30
Ambient temperature [C] -20 -5 0 +10 +23 +30 +40 +50 +60
Correction factor AC version DC version 0,78 0,82 0,83 0,87 0,91 0,95 1,00 1,05 1,11 0,80 0,87 0,90 0,95 1,00 1,05 1,10 1,20 1,30
Example DC version: Rated current at +23C Ambient temperature Correction factor Chosen rated current at +50C ambient temperature 10 A x 1,2 = 12 A
10 A +50C 1,2
Beispiel DC-Version: Nennstrom bei +23C Umgebungstemperatur Korrekturfaktor Gewahlter Nennstrom bei +50C Umgebungstemperatur 10 A x 1,2 = 12 A
10 A +50C 1,2
Tripping characteristic F Auslosekennlinie F
1hr 1000s
Tripping characteristic G Auslosekennlinie G
1hr 1000s
Tripping characteristic H Auslosekennlinie H
1hr 1000s
100s
100s
100s
10s
10s
10s
1s
1s
1s
0,1s
0,1s
0,1s
Tripping time / Auslosezeit
Tripping time / Auslosezeit
1ms
1ms
Tripping time / Auslosezeit 1 10 100 1000 x In
10ms
10ms
10ms
1ms
0,1ms 1 10 100 1000 x In Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
0,1ms Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
0,1ms 1 10 100 1000 x In Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
124
www.schurter.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Tripping characteristic DF Auslosekennlinie DF
1hr 1000s
AS168X
Tripping characteristic DG Auslosekennlinie DG
1hr 1000s
Tripping characteristic DH Auslosekennlinie DH
1hr 1000s
100s
100s
100s
10s
10s
10s
1s
1s
1s
0,1s
0,1s
0,1s
Tripping time / Auslosezeit
Tripping time / Auslosezeit
1ms
1ms
Tripping time / Auslosezeit 1 10 100 1000 x In
10ms
10ms
10ms
1ms
0,1ms 1 10 100 1000 x In Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
0,1ms Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
0,1ms 1 10 100 1000 x In Multiple of rated current (x In) Nennstrom-Vielfaches (x In)
Technical data / Technische Daten
Pole / Pole: Rated voltage Ue Nennspannung Ue AC versions / AC Versionen F; G; H DC versions / DC Versionen DF; DG; DH Note: The connection polarity must be strictly observed. An application with a DC Type AS168X in an AC network is not allowed. Hinweis: Die Anschlusspolaritat muss unbedingt beachtet werden. Eine Anwendung von DC Versionen in AC Netzen ist nicht zulassig. Rated current In Nennstrom In Endurance Lebensdauer Type of tripping Ausloseart Type of actuation / Betatigungsart Permissible wire cross section Zulassiger Leiterquerschnitt See approvals, page 126 Siehe Approbationen Seite 126 Number of cycles at In Anzahl Schaltspiele bei In * Thermal magnetic / thermisch-magnetisch * Positively trip-free / positive Freiauslosung Manual ON/OFF / Manuell EIN/AUS AC/DC 0,5 - 52 A AC/DC 0,5 - 52 A 6000 6000 TM AC 480/277 V; DC 65 V DC 180 V 1 pole / 1polig DC 360 V 2 - 3 pole / 2 - 3polig
S-type / S-Typ 1,5 - 25 mm2 /AWG #16...4 1,5 - 25 mm2 /AWG #16...4
Switched neutral / Schaltbarer, neutraler Pol: Rated voltage Ue / Nennspannung Ue Rated current In / Nennstrom In Function AC 277 V AC/DC 65 A The switched neutral closes with manual closure of the poles and opens automatically with thermal magnetic tripping of the poles.
www.schurter.com
125
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Technical data (continued) / Technische Daten (Fortsetzung)
Funktion
AS168X
Der Neutralleitertrenner schliesst bei manueller Einschaltung der Pole und offnet automatisch bei thermischmagnetischer Auslosung der Pole.
Add-on modules / Zusatzmodule: Rated voltage Ue / Nennspannung Ue Auxiliary contact H1 & H2 and Signal contact S1 & S2 Hilfskontakt H1 & H2 und Signalkontakt S1 & S2 Functional auxiliary contact module AC 277 V DC 125 V DC 50 V Type H1 (assumes the same contact position) Type H2 (assumes the opposite position) Typ H1 (gleichschaltend) Typ H2 (gegenschaltend) Rated current In / Nennstrom In 6A 1A 6A Actuation of the contact is determined by the condition of the handle position of the adjacent poles. Hilfskontakte schalten bei thermischmagnetischer Auslosung sowie Handbetatigung synchron mit den geschutzten Polen. The signal contact operates due to a thermal magnetic tripping and must be reset by hand. Signalkontakte schalten nur bei thermisch-magnetischer Auslosung und sind von Hand zuruckzustellen. Impedance at 50 Hz Impedanz bei 50 Hz 1.1 4.7 16 63 395 When voltage is applied across the terminals, remote tripping takes place by a self interrupting magnetic system. Trip delay time 8 - 16 ms. Beim Anlegen der Klemmenspannung erfolgt die Auslosung durch ein selbstunterbrechendes Magnetsystem. Ausschaltverzogerung 8 - 16 ms.
Funktion Hilfskontakt
Functional signal contact
Type S1 (assumes the same contact position) Type S2 (assumes the opposite position) Typ S1 (gleichschaltend) Typ S2 (gegenschaltend)
Funktion Signalkontakt
Relay trip module Fremdauslosung
Type Typ A1 A2 A3 A4 A5
Voltage range AC/DC Arbeitsbereich AC/DC 5 - 12 V 10 - 24 V 20 - 48 V 40 - 110 V 90 - 240 V
Function of relay trip module
Funktion Fremdauslosung
General data / Allgemeine Daten: Dielectric strength Spannungsfestigkeit Vibration resistance Schwingungsfestigkeit Shock resistance / Stossfestigkeit Protection against electric shock Beruhrungsschutz Permissible ambient temperature Zul. Umgebungstemperatur Weight / Gewichte 1 pole / 1-Pol Switched neutral / Schaltbarer neutraler Pol Auxiliary contact / Hilfskontakt Signal contact / Signalkontakt Relay trip module / Fremdauslosung IEC 60068-2-6, Test Fc AC 2000 V AC 2000 V 0,75 mm amplitude, 10 - 57 Hz 0,75 mm Amplitude, 10 - 57 Hz 25 g / 10 ms Halfsinus IP20 IP20 -20C to +60C -20C bis +60C ca. 130 g ca. 130 g ca. 100 g ca. 100 g ca. 120 g
IEC 60068-2-27, Test Ea Finger safe per IEC 529 Fingerschutz nach IEC 529
126
www.schurter.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Approvals / Approbationen
AC versions / AC-Versionen
DVE
AS168X
VDE EN 60934 *
Poles Characteristic/ Nennstrom [A] Volt AC Volt DC Icn [A] Volt AC
UL UL 1077 CSA 22.2 235
Volt DC Icn [A]
UL UL 508 ** CSA 22.2 14
Volt AC Icn [A]
1
2
3
4
F/G/H 45 - 52 F/G 0.5 - 25 H 0.5 - 40 F/G 27 - 40 F/G/H 45 - 52 F/G 0.5 - 25 H 0.5 - 40 F/G 27 - 40 F/G/H 45 - 52 F/G 0.5 - 25 H 0.5 - 40 F/G 27 - 40 F/G/H 0.5 - 52
420/240 420/240 420/240 420/240 420 420 420 420 420 420 420 420 420/240
65 65 65 65 65 65 65 65 65 65 65 65 65
4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500 4500
277 277 240 277 277 240 480 480 480 480 480Y/277 480Y/277 480Y/277 480Y/277 480Y/277
65
5000 5000 10000 5000 5000 10000 5000 10000 5000 10000 5000 10000 5000 10000 5000
277 277 277 277 480 480 480 480 480 480 480 480 480Y/277
5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000
65 65
65 65 65 65 65 65 65 65 65 65
DC versions / DC-Versionen
DVE
VDE * EN 60934
Poles Characteristic/ Nennstrom [A] Volt DC Icn [A]
UL UL 1077 CSA 22.2 235
Volt DC Icn [A]
1
2
3
4
DF / DG 0.5 - 50 DH 6 - 50 DF / DG 0.5 - 50 DH 6 - 50 DF / DG 0.5 - 40 DF / DG 45 - 50 DH 6 - 50 DF / DG 0.5 - 40 DF / DG 45 - 50 DH 6 - 50
120 120 240 240 360 360 360 360 360 360
4500 4500 4500 4500 4500 4500 4500 4500 4500 4500
180 180 360 360 360 360 360 360 360 360
2000 2000 2000 2000 10000 5000 5000 10000 5000 5000
* VDE approval pending / VDE Zulassung pendent ** Rated currents 32 - 52 A available approx. March 2003 / Nennwerte 32 - 52 A ca. ab Marz 2003 lieferbar www.schurter.com
127
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
AS168X
Conversion table Ampere rating - Horsepower rating / Umrechnungstabelle Ampere - Horsepower Voltage Rating: One pole: Two pole: Three pole: AC 277 V, 1 phase AC 480Y/277 V, 1 phase AC 480Y/277 V, 3 phase
HORSEPOWER (FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN) NOMINAL CIRCUIT VOLTAGE, Vac 380440220110265 277 200 208 415 480 240 120 1 2 pole pole 1/10 1/6 1/4 1/3 1/2 3/4 1 1 1/2 2 2 2 3 3 3 3 5 5 5 5 7 1/2 7 1/2
HP-Rating: 1 phase (1 pole & 2 pole):
AS168X-CB
MOTOR NAMEPLATE
Rated Current (See Note #1) 0.5A 1A 1.5A 2A 3A 4A 5A 6A 7A 8A 9A 10A 12A 13A 15A 16A 18A 20A 23A 25A 27A 30A
FLA Rating 0.5A 1A 1.5A 2A 3A 4A 5A 6A 7A 8A 9A 10A 12A 13A 15A 16A 18A 20A 23A 25A 27A 30A
Starting/ LRC Rating 3 6 9 12A 18A 24A 30A 36A 42A 48A 54A 60A 72A 78A 90A 96A 108A 120A 138A 150A 162A 180A
1/10 1/8 1/6 1/4 1/4 1/3 1/3 1/2 1/2 1/2 3/4 1 1 1 1/2 1 1/2 2 2 2
1/6 1/4 1/3 1/2 1/2 3/4 3/4 1 1 1/2 1 1/2 2 2 2 3 3 3 3 3
1/6 1/3 1/3 1/2 1/2 3/4 1 1 1 1/2 1 1/2 2 2 2 3 3 3 3 3
1/10 1/8 1/4 1/3 1/2 1/2 3/4 1 1 1 1/2 2 2 2 2 3 3 3 3 3 5
1/10 1/6 1/4 1/3 1/2 3/4 1 1 1_ 1 1/2 2 2 3 3 3 3 3 5 5 5
1/10 1/6 1/3 1/3 1/2 3/4 1 1 1 1/2 2 2 2 3 3 3 3 3 5 5 5
1/2 1 1 1/2 2 2 2 3 3 3 3 5 5 5 5 7 1/2 7 1/2 10 10
HP-Rating: 3 phase (3 pole):
AS168X-CB MOTOR NAMEPLATE FLA Rating 0.5A 1A 1.5A 2A 3A 4A 5A 6A 7A 8A 9A 10A 12A 13A 15A 16A 18A 20A 23A 25A 27A 30A Starting/ LRC Rating HORSEPOWER (FLA & LRC RATINGS APPLY WHERE NO HP RATING IS GIVEN) NOMINAL CIRCUIT VOLTAGE, VAC 110-120 200 208 220-240 380-415 440-480 3 pole
Rated Current (See Note #1) 0.5A 1A 1.5A 2A 3A 4A 5A 6A 7A 8A 9A 10A 12A 13A 15A 16A 18A 20A 23A 25A 27A 30A
10A 12.5A 20A 25A 32A 32A 32A 46A 46A 46A 63.5A 63.5A 81A 81A 81A 81A 116A 116A 145A 145A
1/2 1/2 3/4 3/4 1 1 1 1/2 1 1/2 2 2 2 3 3 3 3 3
1/2 3/4 1 1 1 1/2 2 2 2 3 3 3 3 5 5 5 5 7 1/2 7 1/2
1/2 3/4 1 1 1 1/2 2 2 2 3 3 3 3 5 5 5 7 1/2 7 1/2 7 1/2
1/2 3/4 1 1 1/2 2 2 2 3 3 3 3 5 5 5 7 1/2 7 1/2 7 1/2 10
1/2 3/4 1 1 1/2 2 2 3 3 3 5 5 5 7 1/2 7 1/2 10 10 10 10 15 15
1/2 3/4 1 1/2 2 3 3 3 5 5 5 7 1/2 7 1/2 10 10 10 10 15 15 20 20
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loads, AC resistance loads
128
www.schurter.com
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Order code / Bestellcode
Basic type / Grundtyp Thermal magnetic high performance circuit breaker Thermisch-magnetischer Hochleistungs-Gerateschutzschalter Number of poles / Polzahl 1 2 3 4 Tripping characteristics / Auslosekennlinien Thermal Thermisch F G H DF DG DH 1.0 -1.25 xIn 1.0 -1.25 xIn 1.0 -1.25 xIn 1.05 -1.35 xIn 1.05 -1.35 xIn 1.05 -1.35 xIn Magnetic Magnetisch 3 - 5 xIn 6 - 10 xIn 12 - 20 xIn 4,5 - 8 xIn 9 - 16 xIn 18 - 32 xIn
AS168X
Deliverable currents Lieferbare Nennstrome 0,5 - 52 A 0,5 - 52 A 0,5 - 52 A 0,5 - 50 A 0,5 - 50 A 6,0 - 50 A
Rated current / Nennstrom Code 005 010 015 020 030 040 050 In (A) 0.5 1.0 1.5 2.0 3.0 4.0 5.0 Code 060 070 080 090 100 120 150 In (A) 6.0 7.0 8.0 9.0 10.0 12.0 15.0 Code 160 180 200 230 250 270 300 In (A) 16.0 18.0 20.0 23.0 25.0 27.0 30.0 Code 320 350 400 450 500 520 In (A) 32.0 35.0 40.0 45.0 50.0 52.0 *
* AC version only / Nur AC-Version
Switched neutral pole / Schaltbarer neutraler Pol N Maximum combination Maximale Kombinationen
A1... A5/ S1, S2/ H1, H2
A1... A5/ S1, S2/ H1, H2 + 4 poles + N + 4 Pole + N
AS168X - CB 2 DG 200 N AS168X - ACB S2
1 Add-on module 1 Zusatzmodul
2 Add-on modules + 3 poles + N 2 Zusatzmodule + 3 Pole + N
Auxiliary contact / Hilfskontakt H1 H2 Assumes the same contact position as the protected poles Gleiche Kontaktposition wie die geschutzten Pole (gleichschaltend) Assumes the opposite contact position as the protected poles Entgegengesetzte Kontaktposition wie die geschutzten Pole (gegenschaltend)
Signal contact / Signalkontakt S1 S2 Assumes the same contact position as the protected poles Gleiche Kontaktposition wie die geschutzten Pole (gleichschaltend) Assumes the opposite contact position as the protected poles Entgegengesetzte Kontaktposition wie die geschutzten Pole (gegenschaltend)
Relay trip module / Fremdauslosung A1 A2 A3 A4 A5 AC/DC AC/DC AC/DC AC/DC AC/DC 5 - 12 V 10 - 24 V 20 - 48 V 40 - 110 V 90 - 240 V
Accessories / Zubehor Must be ordered separately / muss separat bestellt werden
A1... A5/ S1, S2/ H1, H2
www.schurter.com
129
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
DIN rail mounting / Hutschiene DIN-Befestigung
AS168X-CB1...
45
AS168X
...N
44.4
61.6 68.4
26.6
5.1
35 1.9 90 35 mm DIN rail EN 50022 35 mm Hutschiene DIN-EN 50022
17.5 - 0.0
+0.5
17.5 - 0.0
+0.5
Max. torque Max. zulassiges Anzugsdrehmoment Wire crosssection Drahtquerschnitt 1.5...10 mm2 16 ...25 mm2 AWG #16...8 AWG #6...4 Max. torque Max. Drehmoment 2.5 Nm 3.1 Nm 22 Ib-in 28 Ib-in
AS168X-ACBH.
AS168X-ACBS.
AS168X-ACBA.
90
90
17.5 - 0.0
+0.5
17.5 - 0.0
+0.5
17.5 - 0.0
+0.5
130
www.schurter.com
90
26.6
MANUAL MOTOR CONTROLLER AND SUPPLEMENTARY PROTECTOR MOTOR- UND GERATESCHUTZSCHALTER
Schematic diagrams / Schaltbilder
AS168X
AS168X-CB1...
AS168X-CB1...N
AS168X-CB1... AS168X-ACBH1
AS168X-CB1... AS168X-ACBH2
AS168X-CB1... AS168X-ACBS1
AS168X-CB1... AS168X-ACBS2
AS168X-CB1... AS168X-ACBA.
Accessories / Zubehor
AS168X-ACBLOA
Lockout attachment / Abschliessverriegelung
www.schurter.com
131


▲Up To Search▲   

 
Price & Availability of AS168X-CB1DH500N

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X